1. Function: Converts HSI signal from one HYDAC sensor into 4 individual analogue measurement signals (4-20 mA or 2-10 V) and provides 4 relay outputs. 2. Measuring Range: Dependent on connected sensor. 3. Accuracy: Dependent on connected sensor. 4. Process Connection: Connects to sensor via screw terminals (HSI interface). 5. Output & Supply: 4x analogue output (current or voltage). 4x relay outputs. Supply voltage: 24 V DC ± 10%. Provides 24 V DC to sensor. 6. Electrical Connection: Plug-in terminal blocks (RM 3.5) for all connections. Top hat rail mounting. 7. Certifications: CE mark EN 61000-6-2, EN 61000-6-4. Protection class IP40. 8. Housing: Compact design (142x105x35 mm) for top-hat rail (DIN EN 60715 TH 35). 9. Materials: Not explicitly stated. 10. Options: Standard model. Output mode (current/voltage) selectable via jumper and indicated by LED.