DV-5A Valve Trim, Dry Pilot Actuation, Semi-Assembled, Galvanized, Americas, 540001220A, Tyco Fire Protection Products (Johnson Controls)
Valves & PipingPrice on request
Request pricing and availabilityContact our specialists for details, compatibility and supply options.
Description
Main function: Semi-assembled dry pilot actuation trim for DV-5A valve in single interlock preaction system. Range: For 1 1/2 in. (DN40) and 2 in. (DN50). Max trim pressure: 300 psi. DP-2 dry pilot actuator: max 50 psi pilot, max 300 psi water. Actuation: Dry pilot line pressurized with air/nitrogen. Min. 56 ft (17.1 m) of 1/2 in. pipe equivalent to 207 in³. Min. K5.6/80 pilot sprinklers. MC-1 manual stations. Air maintenance device required (AMD-1, AMD-2, or AMD-3). Components: MRA-1, MC-2, AD-3, DP-2 dry pilot actuator, priming restriction, pressure relief valves, ball/globe/check valves, Y-strainer, angle valves, drip funnel, gauges (water 300psi, air 80psi), tubing, fittings. Certifications: UL/FM (with valve). Materials: Galvanized. Options: Pressure switches separately ordered.
Specifications
| Category | Valves & Piping |
| Product ID | 6886455365-4946 |
| Manufacturer | Tyco |